| 品牌Hawke |
Hawke铠装防爆格兰密封接头(501/453/RAC系列)
HAWKE 501/453/RAC CABLE GLANDS
HAWKE铠装防爆格兰(501/453/RAC CABLE GLANDS)
Hazardous Area Cable Glands from Hawke
Hazardous Area Cable Glands-ATEX IECEX,Exe,Exd Group II
Hawke防爆格兰代理商:上海颐品自动化科技有限公司(4008552521)
关键词:Hawke防爆格兰,Hawke防爆变径,Hawke防爆堵头,Hawke防爆呼吸阀,Hawke防爆接线盒,Hawke防爆控制箱
Hawke防爆格兰等产品规格书及相关证书-请咨询上海颐品自动化科技有限公司
Hawke 501/453/RAC cable glands are suitable for use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.
Hawke 501/453/RAC cable glands are dual certified Exd and Exe and suitable for installation in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC, 3.2-91.6mm outside cable diameters.
When used in increased safety applications the Hawke cable gland can be used to terminate braided cables where the braid and the cable outer sheath enter into the electrical enclosure or junction box.
♦ Exdb IIC Gb, Exeb IIC Gb, Extb IIIC, Db Aromoured Cables ATEX & IECEx Cable Gland.
Hawke 501/453/RAC cable gland is suitable for cable termination and installation in Zone 1 (21), Zone 2 (22) and Division 2 hazardous areas.
- Flameproof AExd IIC Gb,
- Increased Safety AExe IIC Gb
- Dust AExtD Zone 21
- Dual Certified Cable Gland For Hazardous Areas ATEX – IECEx
HAWKE 501/453/RAC CABLE GLAND TECHNICAL SPECIFICATION
- Hazardous Area Cable Gland Classification – Exdb IIC Gb, Exeb IIC Gb, Extb IIIC Db
- Certificate No’s – baseefa06ATEX0056X and IECEx BAS 06.0013X
- Cable Gland Zone Location – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC
- Construction and Test Standards – IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31
- Ingress Protection – IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X
- Deluge Protection – DTS01
- Operating Temperature Range -60°C to +100°C
CABLE GLAND SELECtION TABLE FOR HAWKE 501/453/RAC
| Hawke Size Ref. |
Entry Thread Size | Thread Length ‘H’ |
Cable Acceptance Details | ‘G’ Comp ressed Length |
Hexagon Dimensions | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Inner Sheath ‘A’ | Outer Sheath ‘B’ | ‘C’ Armour/Braid | |||||||||||||
| Standard Seal | Alternative Seal (S) | ||||||||||||||
| Metric | NPT * | ||||||||||||||
| Standard | Option | Min. | Max. | Min. | Max. | Min. | Max. | Orienta tion 1 |
Orienta tion 2 |
Across Flats | Across Corners | ||||
| Os | M20 ‡ | ½” | – | 15 | 3.0 | 8.0 | – | – | 5.5 | 12.0 | 0.8 / 1.25 | 0 / 0.8 | 52.0 | 24.0 | 26.5 |
| O | M20 ‡ | ½” | – | 15 | 6.5 | 11.9 | – | – | 9.5 | 16.0 | 0.8 / 1.25 | 0 / 0.8 | 52.0 | 24.0 | 26.5 |
| A | M20 | ¾” | ½” | 15 | 10.0 | 14.3 | 9.0 | 13.4 | 12.5 | 20.5 | 0.8 / 1.25 | 0 / 0.8 | 53.0 | 30.0 | 32.5 |
| B | M25 | 1″ | ¾” | 15 | 13.0 | 20.2 | 9.5 | 15.4 | 16.9 | 26.0 | 1.25 / 1.6 | 0 / 0.7 | 59.5 | 36.0 | 39.5 |
| C | M32 | 1¼” | 1″ | 15 | 19.5 | 26.5 | 15.5 | 21.2 | 22.0 | 33.0 | 1.6 / 2.0 | 0 / 0.7 | 64.0 | 46.0 | 50.5 |
| C2 | M40 | 1½” | 1¼” | 15 | 25.0 | 32.5 | 22.0 | 28.0 | 28.0 | 41.0 | 1.6 / 2.0 | 0 / 0.7 | 68.3 | 55.0 | 60.6 |
| D | M50 | 2″ | 1½” | 15 | 31.5 | 44.4/42.3 † | 27.5 | 34.8 | 36.0 | 52.6 | 1.8 / 2.5 | 0 / 1.0 | 79.0 | 65.0 | 70.8 |
| E | M63 | 2½” | 2″ | 15 | 42.5 | 56.3/54.3 † | 39.0 | 46.5 | 46.0 | 65.3 | 1.8 / 2.5 | 0 / 1.0 | 78.4 | 80.0 | 88.0 |
| F | M75 | 3″ | 2½” | 15 | 54.5 | 68.2/65.3 † | 49.5 | 58.3 | 57.0 | 78.0 | 1.8 / 2.5 | 0 / 1.0 | 83.7 | 95.0 | 104.0 |
| G | M80 | 3½” | – | 20 | 67.0 | 73.0 | – | – | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 95.6 | 106.4 | 115.0 |
| H | M90 | 3½” | – | 20 | 67.0 | 77.6 | – | – | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 95.6 | 115.0 | 130.0 |
| J | M100 | 4″ | – | 20 | 77.0 | 91.6 | – | – | 88.0 | 104.5 | 2.5 / 4.0 | 0 / 1.0 | 95.6 | 127.0 | 142.0 |
All dimensions in millimetres (except*).
Os – F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering.
† Smaller value is applicable when selecting reduced NPT entry option.
Sizes Os and O are available with an M16 thread size. For O size with an M16 thread, the maximum cable inner sheath diameter is 10.9mm.
CABLE GLAND MATERIAL & FINISH
Hawke 501/453/RAC cable glands are manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
PREPARING CABLE & GLAND FOR INSTALLING HAWKE 501/453/RAC

CABLE PREPARATION
Strip Cable to suit equipment as shown above and expose the armour/braid ‘I’.
‘I’ = 20mm for cable gland sizes Os to C ‘I’ = 25mm for cable gland sizes C2 to F ‘II’ = to suit equipment. If required, fit shroud.
CABLE GLAND PREPARATION
Push the cable through the armour spigot (4). Spread armour/braid over the armour spigot (4) until the end of the armour/braid is up against the shoulder of the armour cone. Position the armour clamping ring (3).
Remove the inner seal (5) from the entry (6). Place the entry (6) over the armour spigot (4). Move the sub-assembly (1) and (2) up to meet the entry (6). Note: If the equipment has a threaded entry, it may be advisable to screw the entry component into the equipment to prevent twisting of the cable after step D
Hawke Cable Glands to view the complete range of hazardous area glands certified according to ATEX & IECEx for Zone 1 / Zone 2.
Flameproof Exdb and Increased Safety Exeb (Dust Extb) Dual Certified glands from Hawke include – for further inbation review the product pages or contact us to discuss your cable gland requirements.
- 501/421 Cable Gland Unarmoured – outer cable sheath cable sealing
- 501/423 Cable Gland Unarmoured – flameproof seal to inner/outer cable sheath with IP seal on the outer sheath
- 501/453 Universal Cable Gland Wire Armoured Baided Steel Tape Armoured – indoor/outdoor hazardous areas
- ICG 623 Barrier Gland Unarmoured – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC hazardous areas
- ICG 653 Barrier Gland Armoured – Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC hazardous areas
Hazardous Area Cable Glands-ATEX IECEX,Exe,Exd Group II
Hawke防爆格兰代理商:上海颐品自动化科技有限公司(4008552521)
关键词:Hawke防爆格兰,Hawke防爆变径,Hawke防爆堵头,Hawke防爆呼吸阀,Hawke防爆接线盒,Hawke防爆控制箱
Hawke防爆格兰等产品规格书及相关证书-请咨询上海颐品自动化科技有限公司
- 公司类型私营有限责任公司
- 经营模式生产加工-私营有限责任公司
- 联系人张凯文
- 联系手机13818772521
- 联系固话021-60486851
- 公司地址上海市金山区山阳镇浦卫公路16393号5幢346室
-
天联阻燃屏蔽铠装屏蔽控制电缆WD-MKYJYP33-12*1.5 ¥3.00 -
长期回收正辛酸 甲硫基丁醛 ¥18800.00 -
带煤安证矿用通信光缆MGTSV-8B1 ¥3.00 -
国六新款长安V3冷藏车生产厂家 ¥10000.00 -
高价回收老人牌环氧漆4514P 氯代丁二酰亚胺 ¥18600.00 -
天联矿用通讯电缆MHYV-1*2*7/0.43 ¥13.00 -
天联牌矿用阻燃光缆MGTSV-96B1呼兰 ¥5.00 -
天联矿用通讯电缆MHYVP10*2*7/0.37 ¥3.00 -
天联低烟无卤阻燃控制电缆WD-MKYJYR-5*1 ¥13.00 -
4米2国六江淮领跑S6新能源冷藏车详细价格 ¥10000.00 -
矿用阻燃光纤MGXTSV-4B执行标准MT/T386-2011 ¥3.00 -
天联控制电缆WD-MKYJYP-450/750-14*0.75 ¥13.00 -
大量回收环戊酮 改性通用环氧厚浆漆 ¥18800.00 -
大量回收硫化红棕B3R 弱酸性嫩黄G ¥18600.00 -
深泽天联牌-光缆MGTSV-14B ¥13.00
家家通
进入店铺
店铺留言